• Specific Year
    Any

BUILDING REGULATIONS 2012 - REG 31BA

BUILDING REGULATIONS 2012 - REG 31BA

31BA .         Applicable building standards for buildings and incidental structures in bush fire prone areas (s. 3, 19(3), 37(1) and (2), 57(3), 49(b), 51(2) and (3))

        (1A)         In this regulation —

        bush fire standard means —

            (a)         a bush fire performance requirement; or

            (b)         to the extent not covered by paragraph (a), a requirement imposed under any written law that is a requirement relating to —

                  (i)         a technical aspect of the construction of a building or incidental structure; and

                  (ii)         bush fires;

        Note for this definition:

                Paragraph (b) includes, for example, requirements imposed under the Building Regulations 1989 .

        excluded building work means building work that is the renovation, alteration, extension, improvement or repair of a relevant building if —

            (a)         the estimated value of the building work is less than $20 000; or

            (b)         the renovation, alteration, extension, improvement or repair does not increase the risk of ignition from bushfire attack for the relevant building;

        relevant building means a Class 1, Class 2 or Class 3 building that was not required to comply or substantially comply with a bush fire standard at the latest of the following times —

            (a)         when the building was constructed;

            (b)         if 1 or more applications or notices under section 49(b) or 51(2) or (3) or regulation 47(1) have been made or given in respect of the building — when the application or notice, or the last application or notice, was made or given;

            (c)         if the building has been relocated — when the building was last relocated;

        renovation, alteration, extension, improvement or repair , in respect of a building, does not include the installation of a roof mounted evaporative air conditioning unit on the building.

        (1)         For the purposes of the definition of applicable building standard in section 3, the building standards set out in Column 2 of the Table are prescribed as applicable building standards for the purposes set out in Column 1 of the Table opposite the standards.

Table

Item

Column 1

Purposes

Column 2

Applicable building standards

1.

Section 19(3) in respect of all kinds of buildings and incidental structures located in a bush fire prone area

The requirements mentioned in regulation 31A(2) except that the bush fire performance requirements are not applicable building standards if —

(a)         the building or incidental structure is or will be located in an area that, at any time during the 4‑month period ending on the day on which the application is made, was not a bush fire prone area; or

(b)         the building work that is proposed to be done in respect of the building or incidental structure is excluded building work only; or

(c)         the building or incidental structure is or will be —

(i)         a Class 10a building or deck; and

(ii)         associated with a relevant building.

2.

Section 37(1) in respect of all kinds of buildings and incidental structures located in a bush fire prone area

The requirements mentioned in regulation 31A(2) except that the bush fire performance requirements are not applicable building standards if —

(a)         the building or incidental structure is located in an area that, at any time during the 4‑month period ending on the day on which the application for the building permit was made, was not a bush fire prone area; or

(b)         the building work done in respect of the building or incidental structure under the building permit is excluded building work only; or

(c)         the building or incidental structure is —

(i)         a Class 10a building or deck; and

(ii)         associated with a relevant building.

Note for this item:

See also regulation 31HB(2).

3.

Section 37(2) in respect of all kinds of buildings and incidental structures located in a bush fire prone area

The requirements mentioned in regulation 31E(2) except that the bush fire performance requirements are not applicable building standards if —

(a)         the building or incidental structure is located in an area that, at any time during the 4‑month period ending on the day on which the building work in respect of the building or incidental structure commenced, was not a bush fire prone area; or

(b)         the building work done in respect of the building or incidental structure is excluded building work only; or

(c)         the building or incidental structure is —

(i)         a Class 10a building or deck; and

(ii)         associated with a relevant building.

Note for this item:

See also regulation 31HB(3).

4.

Section 57(3) for an application mentioned in section 49(b) in respect of all kinds of buildings located in a bush fire prone area

The requirements mentioned in regulation 31G(2) except that the bush fire performance requirements are not applicable building standards if the building is located in an area that, at any time during the 4‑month period ending on the day on which the application is made, was not a bush fire prone area.

5.

Section 57(3) for an application mentioned in section 51(2) in respect of all kinds of buildings located in a bush fire prone area

The requirements mentioned in regulation 31G(2) except that the bush fire performance requirements are not applicable building standards if —

(a)         the building is located in an area that, at any time during the 4‑month period ending on the day on which the application is made, was not a bush fire prone area; or

(b)         the unauthorised work done in respect of the building is excluded building work only.

6.

Section 57(3) for an application mentioned in section 51(3) in respect of all kinds of buildings and incidental structures located in a bush fire prone area

The requirements mentioned in regulation 31G(2) except that the bush fire performance requirements are not applicable building standards if —

(a)         the building or incidental structure is located in an area that, at any time during the 4‑month period ending on the day on which the application is made, was not a bush fire prone area; or

(b)         the unauthorised work done in respect of the building or incidental structure is excluded building work only; or

(c)         the building or incidental structure is —

(i)         a Class 10a building or deck; and

(ii)         associated with a relevant building.

        (2)         Item 1, 2 or 3 (as the case may be) of the Table to subregulation (1) does not apply if the building work is the assembly, reassembly or securing of a relocated building or a relocated incidental structure.

        Note for this subregulation:

                See also regulation 31D.

        (3)         Column 2 paragraph (b) of item 1, 2, 3, 5 or 6 (as the case may be) of the Table to subregulation (1) does not apply if the excluded building work is part of a larger project of building work that has been divided up for the sole or dominant purpose of taking advantage of that paragraph.

        (4)         In determining whether building work is excluded building work for the purposes of Column 2 paragraph (b) of item 2 or 3 (as the case may be) of the Table to subregulation (1), the definition of that term in subregulation (1A) applies as if the definition of relevant building had not been replaced by the Building Amendment Regulations 2021 regulation 6(1) and (2) if —

            (a)         in the case of item 2 — the building permit for the building work was obtained before 1 May 2021; or

            (b)         in the case of item 3 — the building work commenced before 1 May 2021.

        [(5)-(8)         deleted]

        [Regulation 31BA inserted: Gazette 7 Dec 2015 p. 4898‑900; amended: Gazette 5 Apr 2016 p. 1017‑19; 9 Mar 2018 p. 800; 26 Mar 2019 p. 943; SL 2021/42 r. 6; SL 2022/26 r. 7.]

[ 31B.         Deleted: Gazette 5 Oct 2018 p. 4014.]