BUILDING REGULATIONS 2018 (SR NO 38 OF 2018) - REG 147 Shared accommodation buildings—automatic fire suppression systems

BUILDING REGULATIONS 2018 (SR NO 38 OF 2018) - REG 147

Shared accommodation buildings—automatic fire suppression systems

    (1)     This regulation applies to a Class 3 building that is a shared accommodation building constructed, or for which a building permit was granted, before 1 July 2003.

    (2)     A fire sprinkler system in accordance with deemed-to-satisfy provisions contained in clause E1.5 of the BCA Volume One must be installed throughout a shared accommodation building.

    (3)     This regulation must be complied with by the owner of the building.

    (4)     This regulation does not apply to a shared accommodation building that has a rise in storeys of not more than 2 and—

        (a)     the distance of travel from the entrance doorway of each sole-occupancy unit is not more than 6 m—

              (i)     to the nearest exit; or

              (ii)     to a point from which travel in different directions to at least 2 exits is available; and

        (b)     that has a fire hose reel system in accordance with the deemed-to-satisfy provisions contained in clause E1.4 of the BCA Volume One or, in the case of a fire compartment having a floor area not greater than 500 m 2 , portable fire extinguishers to cover Class A fire risks in accordance with AS 2444—2001 Portable fire extinguishers and fire blankets—Selection and location as in force or as issued or published from time to time; and

        (c)     that has emergency lighting in accordance with the deemed-to-satisfy provisions contained in clause G4.4 or clause E4.2 of the BCA Volume One (as appropriate); and

        (d)     that has exit signs in accordance with the deemed-to-satisfy provisions contained in Part E4 of the BCA Volume One; and

        (e)     that has a management plan in accordance with Practice Note 2008-13 issued by the Building Commission in November 2008.

    (5)     This regulation does not apply to a shared accommodation building that has a rise in storeys of more than 2 and—

        (a)     the distance of travel from the entrance doorway of each sole-occupancy unit—

              (i)     to the nearest exit; or

              (ii)     to a point from which travel in different directions to at least 2 exits is available—

is not more than 6 m; and

        (b)     that has building elements with a fire-resistance level of not less than 60/60/60 separating each sole-occupancy unit from—

              (i)     a public corridor, public lobby or the like; or

              (ii)     a room not within the sole-occupancy unit; or

              (iii)     the landing of an internal non-fire-isolated stairway; or

              (iv)     another sole-occupancy unit; and

        (c)     any doorways from each sole-occupancy unit that provide access to a public corridor, public stairway, internal non-fire-isolated stairway or the like are protected with a self-closing fire door having a fire-resistance level of not less than -/30/30; and

        (d)     that has a fire hose reel system in accordance with the deemed-to-satisfy provisions contained in clause E1.4 of the BCA Volume One; and

        (e)     that has emergency lighting in accordance with clause G4.4 or clause E4.2 contained in the BCA Volume One (as appropriate); and

        (f)     that has exit signs in accordance with the deemed-to-satisfy provisions contained in Part E4 of the BCA Volume One; and

        (g)     that has a management plan in accordance with Practice Note 2008-13 issued by the Building Commission in November 2008.

    (6)     This regulation does not apply to a shared accommodation building—

        (a)     in which—

              (i)     each storey that has sleeping facilities has its own direct egress to a street or to open space; and

              (ii)     the distance of travel from the entrance doorway of each sole-occupancy unit to the nearest exit, or to a point from which travel in different directions to at least 2 exits is available, is not more than 6 m; or

        (b)     that was constructed, or for which a building permit was granted, before 1 August 1997; or

        (c)     that has an approved automatic fire suppression system installed throughout the building.