ENVIRONMENTAL PLANNING AND ASSESSMENT REGULATION 2000 - REG 180 Supplementary fire safety statement to be given to council and Fire Commissioner and prominently displayed in building

ENVIRONMENTAL PLANNING AND ASSESSMENT REGULATION 2000 - REG 180

Supplementary fire safety statement to be given to council and Fire Commissioner and prominently displayed in building

180 Supplementary fire safety statement to be given to council and Fire Commissioner and prominently displayed in building

(cf clause 80GD of EP[#38]A Regulation 1994)

(1) The owner of building premises in which a critical fire safety measure is implemented must cause the council to be given periodic supplementary fire safety statements for that measure.
(2) A supplementary fire safety statement for a critical fire safety measure must be given at such intervals (being intervals of less than 12 months) as is specified in respect of that measure in the current fire safety schedule for the building.
(2A) Failure to give a supplementary fire safety statement to the council within the time required by the current fire safety schedule for the building constitutes a separate offence for each week beyond the expiry of that time for which the failure continues.
(3) As soon as practicable after a supplementary fire safety statement is issued, the owner of the building to which it relates--
(a) must cause a copy of the statement (together with a copy of the current fire safety schedule) to be given to the Fire Commissioner, and
(b) must cause a further copy of the statement (together with a copy of the current fire safety schedule) to be prominently displayed in the building.
(4) Subclause (3)(b) ceases to apply to a supplementary fire safety statement only when every critical fire safety measure with which it deals has become the subject of a later fire safety certificate or fire safety statement.